No. 9, Longding Road, Industrial Cluster Zone, Yichuan County, Luoyang City, China

PRODUCT

S13 Series Oil-Immersed Transformers

Oil-immersed Transformer S13-M

Full Technical Parameters (Standard Version)

1. General Data
– Type: Oil-immersed, fully sealed, S13 energy-saving type                                                                                                           – Phase: 3-phase
– Frequency: 50 Hz                                                                                                                                                                                  – Rated Voltage (HV): 10 kV, 11 kV
– Rated Voltage (LV): 0.4 kV (400/230 V)                                                                                                                                         – Connection Group: Dyn11 (standard)
– Cooling Method: ONAN (Oil Natural Air Natural)                                                                                                                         – Insulation Class: A
– Service Conditions: Indoor / Outdoor

2. Rated Capacity Range

100, 200, 315, 400, 500, 630, 800, 1000, 1250, 1600, 2000 kVA

3. Voltage & Taps

– HV Tap Changer: Off-circuit tap changer (no-load)                                                                                                                     – Tap Range: ±2×2.5%
– Voltage Regulation Accuracy: ±0.5%

4. Losses (S13 GB Standard)

– 100 kVA: No-load Loss 130 W, Load Loss 1580 W, No-load Current 0.7%                                                                             – 200 kVA: No-load Loss 220 W, Load Loss 2600 W, No-load Current 0.6%
– 315 kVA: No-load Loss 360 W, Load Loss 4300 W, No-load Current 0.55%                                                                          – 400 kVA: No-load Loss 380 W, Load Loss 4800 W, No-load Current 0.5%
– 500 kVA: No-load Loss 510 W, Load Loss 6100 W, No-load Current 0.5%                                                                             – 630 kVA: No-load Loss 570 W, Load Loss 6200 W, No-load Current 0.45%
– 800 kVA: No-load Loss 670 W, Load Loss 7500 W, No-load Current 0.45%                                                                         – 1000 kVA: No-load Loss 800 W, Load Loss 10300 W, No-load Current 0.4%
– 1250 kVA: No-load Loss 980 W, Load Loss 12000 W, No-load Current 0.4%                                                                       – 1600 kVA: No-load Loss 1200 W, Load Loss 14500 W, No-load Current 0.35%
– 2000 kVA: No-load Loss 1360 W, Load Loss 18300 W, No-load Current 0.35%

5. Impedance Voltage

– ≤ 630 kVA: 4.0%                                                                                                                                                                                   – ≥ 800 kVA: 4.5%

6. Insulation Level

– HV: LI75AC35 (for 10 kV class)                                                                                                                                                          – LV: ≤ 2 kV

7. Temperature Rise

– Winding: 65 K                                                                                                                                                                                        – Top Oil: 55 K
– Ambient Temperature: -25°C ~ +40°C

8. Oil Tank & Structure

– Tank Material: Steel plate, welded, corrosion-resistant                                                                                                               – Oil Type: Transformer oil 25#
– Sealing Type: Fully sealed structure                                                                                                                                                 – Corrosion Protection: Sandblasting + epoxy primer + topcoat

9. Accessories (Standard)

– Oil level indicator                                                                                                                                                                                  – Pressure relief valve
– Thermometer pocket                                                                                                                                                                            – Earthing bolt
– HV / LV bushing
– Lifting lugs                                                                                                                                                                                              – Nameplate

10. Standards Compliance

– IEC 60076
– GB/T 1094
– GB/T 6451-2023
– GB 20052-2024 (Energy efficiency Level 2)

11. Protection Class

– IP00 (open type)
– IP20 (with enclosure, optional)

Application scope:

Urban and rural distribution network construction and renovation, residential communities, commercial districts, mines, metallurgy, chemical industry, machinery manufacturing, highways, railways, airports, ports, and new energy supporting fields.

 

S13 Oil-immersed Transformer

🔹 Main Application Areas

– Urban & Rural Power Grid Reconstruction & Expansion
– Industrial & Mining Enterprises Power Supply
– Commercial Buildings, Residential Quarters & Infrastructure
– Petroleum, Chemical, Metallurgy & Textile Industries
– Schools, Hospitals, Malls & Data Centers
– Wind & Solar PV Power Generation Step-up/step-down Systems
– Construction Sites, Temporary & Emergency Power Supply

🔹 Suitable Environment

– Indoor / Outdoor Installation
– Altitude: ≤1000m (Customizable for Higher Altitude)
– Ambient Temperature: -25℃ ~ +40℃
– Relative Humidity: ≤95%
– Vibration-free & Non-corrosive Gas Environments

🔹 Voltage & Capacity Application

– Rated Voltage: 6kV, 10kV, 11kV, 35kV Distribution System
– Rated Capacity: 30–2500 kVA
– Widely Used in 10kV/0.4kV Distribution Network

🔹 Application Advantages

✅ High Energy Efficiency, Low No-load Loss
✅ Fully Sealed, Maintenance-free, Long Service Life
✅ Low Noise, Stable Operation, High Reliability
✅ Strong Short-circuit Withstand Capacity, Safe & Durable